Product Description
Product Description
The E-Mon D-Mon® Class 3200 meter is a 3-element meter with communications. The device is used to monitor electric power usage of individual loads (after the utility meter) and store kW and kVAR data for automatic meter reading. It provides real-time monitoring of kWh, kW demand, power factor, voltages, and amperages.
Application
APPLICATION
As an integrated BAS component these meters allow for advanced energy monitoring and control features such as demand limiting, demand response, and load response.
Specifications
SPECIFICATIONS
Mounting
- Surface mounted within a NEMA 4X rated enclosure
- Multiple Meter Unit
Dimensions
- Height: 7.75 inches
- Width: 7.75 inches
- Depth: 4.0 inches
Power Requirements
- Input Voltage Configuration: 3-wire (delta)
- or 4-wire (wye)
- Mains Voltage Input: Up To 600 VAC RMS available
- Input Power: 6 VA maximum
- Current Sensor Rating: Up To 3200 amps
- RMS AC available
- Power Factor: 0.5 leading or lagging
- Line Frequency: 50-60 Hz
- Voltage Overload +25% continuously: +100% For 20 cycles
- Current Sensor Overload: 100% for 1 minute
Standard Ranges
- 4-Wire Wye: 208 VAC: 100, 200, 400, 800,1600 Amp
- 3-Wire Delta: 240 VAC: 100, 200, 400, 800,1600 Amp
- 4-Wire Wye: 480 VAC: 100, 200, 400, 800,1600 Amp
- 3-Wire Delta: 480 VAC: 100, 200, 400, 800,1600 Amp
- 4-Wire Wye: 600 VAC: 100, 200, 400, 800,1600 Amp
Communications
- Method: RS-485
- Application Protocol:
- Modbus RTU max 38.4 Kbps
- BACnet MS/TP max 38.4 Kbps
- RS-232 (local computer communication only)
LED Indicators
Operating Environment
- Temperature: -20C to +50C
- Relative Humidity Range: 0-95% non-condensing
Approvals
- Listed device: CUL/UL (Listed to latest applicable standards for safety)
- Metering Accuracy: ANSI C12.20
- NEMA 4X
Application Requirements
- Opus Version 5.5 or higher
- Application Version 4.0 or higher
Product Order Numbers
PRODUCT ORDER NUMBERS
Name
Product Description
Order Number
Part and Model Numbers are required in ordering. Model numbers vary based on the configuration selected. Below are the available configuration options and an example of the part/model number.