English Chinese (Simplified) French Portuguese Spanish
AddThis Social Bookmark Button

Opus xcm.20R Executive Controller/Server

  • XCM 20RWebMainProduct Description


    The Opus XCM 20R functions as an open Building Automation System (BAS) network manager that combines integrated control, supervision, data logging, alarming, and scheduling into a single controller platform. The XCM 20R is designed to integrate diverse devices into a seamless system, as it supports a wide range of open protocols, including BACnet®, MODBUS® and LonWorks®. The XCM 20R also supports NovarNet protocol and is backward compatible with most Novar Logic One and Spectrum field controllers.

    acrobatjpgDownload xcm.20R Sell Sheet Here

     

  • Application

    BAS supervisory control for HVAC, lighting and energy management applications within large buildings.  The XCM.20R is ideal for applications that require a local touch screen user interface and inputs/outputs that are centrally located with the Executive Controller. The XCM20R includes an integrated enclosure and is compatible with legacy Logic One EnvoiXE, EP2 and all Lingo baseplates, making upgrades easy.

  • Specifications

    Mounting
    Compatible with the following surface mounted baseplates:
    • XCM 20R (new installations)
    • EP2, Lingo
    • Lingo XE
    • Envoy XE
    Dimensions
    • Height: 13 inches
    • Width: 12.5 inches
    • Depth: 2.0 inches
    Power Requirements
    • Input: 24 VAC, Class 2 (22 to 28 VAC),
    • Frequency: 50/60 Hz
    • Consumption: 40 VA
    • Protection: all inputs/outputs protected against high voltage surge and transients
    Inputs
    • 8 Universal
      • Thermistor: Type 3, 10K 14 to 212 F
      • Voltage: 0-10VDC, input impedance >5K ohms
      • Current: 4-20mA, input impedance >5Kohms, loop source 20-24VDC
      • Digital: contact closure or pulse, open circuit voltage 5VDC, dry contact wetting current 4mA, max pulse count frequency 20Hz @ 50% duty cycle
    Outputs
    • 4 Digital:
    • 24VAC or DC, 2 amps, Class 2 SPDT relay outputs
    Diagnostics
    • 5 integrated diagnostic points for monitoring internal and external power supplies, system ambient temperature and transformer ground fault status
      Communications
    • 6 RS-485 Ports (non isolated; optimized failsafe biasing provided on all ports)
      • Application Protocol
        • NovarNet : 1.7-9.6 kBd (biasing may be required)
        • BACnet MSTP: max 76.8 Kbps
        • Modbus RTU: 38.4 Kbps
    • 1 (Optional) LonWorks Port using additional optional card: max 76.8 kbps
    • 1 RS-232 Port: 9-pin D-shell connector for serial shell mode access
    • 2 Ethernet Ports: 10/100 Mbps
      • Application Protocol
        • BACnet IP
        • Modbus TCP
        • Niagara Network (Fox)
        • oBix
    LED Indicators
    • Output
    • Power
    • Module Communications
    • Network Communications
    Operating Environment
    • Temperature: 32°F to 122°F (0°C to 50°C)
    • Humidity: 10 to 90% Relative, non-condensing
    Approvals
    • Listed device: CUL/UL E90949; UL R/C E134292
    • Standards used: Module is UL listed as PAZX and PAZX7 per UL916 and also UL Recognized Component as SDFY2 and SDFY8 per UL 873, “Signal Equipment”, CE, FCC Part 15, Class A
    • International:CE, C-Tick, and WEEE
    Application Requirements
    • Opus Version 5.5 or higher
    • Application Version 4.0 or higher
    • Xcm20Rio.jar version 1.1 or higher

  • NameProduct DescriptionOrder Number
    XCM20R-RC-C RC Base Cover XCM20R-RC-C
    XCM20R-EP2-C EP/2 Cover XCM20R-EP2-C
    XCM20R-LINGO-C Lingo Cover XCM20R-LINGO-C
    XCM20R-LXE-C Lingo XE Cover XCM20R-LXE-C
    XCM20R-BPL-C XCM20R Base Cover XCM20R-BPL-C
    XCM20R-BPL XCM20R Base (includes transition board and cover) XCM20R-BPL
    XCM20R-BPL-TRAN XCM20 BPL Transition board XCM20R-BPL-TRAN
    XCM20R-RC-KIT RC Upgrade Kit (includes adaptor board and RC cover) XCM20R-RC-KIT
    XCM20R-RC-ADP RC upgrade adaptor board XCM20R-RC-ADP
    XCM20R-C-BFU Color display, BACnet, FOX, UI XCM20R-C-BFU
    XCM20R-C-BFUM Color display, BACnet, FOX, UI, Modbus XCM20R-C-BFUM
    XCM20R-C-BFUMI Color display, BACnet, FOX, UI, Modbus & Modbus TCP XCM20R-C-BFUMI
    XCM20R-C-BLFU Color display, BACnet, Lon, FOX, UI XCM20R-C-BLFU
    XCM20R-C-BLFUM Color display, BACnet, Lon, FOX, UI, Modbus XCM20R-C-BLFUM
    XCM20R-C-BLFUMI Color display, BACnet, Lon, FOX, UI, Modbus & Modbus TCP XCM20R-C-BLFUMI
    XCM Battery Replacement Battery for all XCMs NPB-BATT