English Chinese (Simplified) French Portuguese Spanish
AddThis Social Bookmark Button

Opus® XIO BACnet® Remote I/O

  • Product Description

    • The Opus® XIO series of BACnet® Remote I/O Modules are designed and optimized to expand the I/O points available to the Opus XCM family of Executive Controller Modules. When configured using Opus Supervisor, each XIO Remote I/O Module increases the available I/O point count of an Opus Executive by eight I/O points.
  • Application

    XIO Remote I/O Modules feature can control an assortment of HVAC and lighting applications as well as monitor any digital or analog point. All XIO Modules communicate via BACnet to Novar’s Opus BAS, enabling them to be easily integrated with other control functions.

    Features:

    • BACnet MS/TP Communication protocol for easy integration
    • Universal inputs and Form C relay outputs interface with a wide variety of sensors and actuators
    • Available with HOA switches
    • Universal Inputs can also be used as Analog Outputs
    • Fused outputs reduce installation labor and panel space
    • 24V Power and BACnet communication expansion connectors minimize the need for daisy chain wiring in multi-module installations
  • Specifications

    Mounting
    DIN rail mount or panel mount in any orientation using four slotted screw holes

    Dimensions (xio.80/xio.80CT Modules)
    • Height: 5.53 inches (141mm)
    • Width: 5.64 inches (143mm)
    • Depth: 1.84 inches (47mm)
    • Weight: 0.60 lb
    Dimensions (xio.08/xio.08H/xio.44/xio.44H Modules)
    • Height: 5.53 inches (141mm)
    • Width: 6.64 inches (169mm)
    • Depth: 1.98 inches (50mm)
    • Weight: 0.95 lb
    Operating Environment
    • Operating Temp: -40ºF to 158ºF (-40ºC to 70ºC)
    • Storage Temp: -40ºF to 158ºF (-40ºC to 70ºC)
    • Humidity: 5% to 95% RH, non-condensing
    Power Requirements
    • Input: 22 VAC - 28VAC, Class 2
    • Frequency: 50/60HZ
    • Consumption: 10VA, 4VA (xio.80CT only)
    Inputs
    • Thermistor Mode:
      • Novar refrigeration 2K, useable range -49°F to 102°F (-45°C to 39°C)
      • PRECON Type 2, 10K, useable range 14°F to 212°F (-10°C to 100°C)
      • PRECON Type 3 10K, useable range 14°F to 212°F (-10°C to 100°C)
      • Honeywell 20K, usable range 41°F to 186.8°F (5°C to 86°C)
    • Voltage Mode:
      • 0-10VDC, Input impedance > 5Kohms
      • Accuracy = +/- 2% of full scale
    • Current Mode:
      • 4-20mA, Input impedance approximately 500 ohms, Accuracy = +/-1% of full scale.
    • Resistance Mode:
      • 100 – 100K Ohms, Accuracy +/- 2% of reading over 1K - 100K Ohm range.
    • Pulse Counting Mode:
      • Maximum pulse counting frequency = 20Hz @ 50% duty cycle
    • Current Transformer Inputs:
      • Range 0-5A, Accuracy +/-5% at span, Resolution = 100mA
      Outputs
    • 5A @ 240Vac, all outputs on, up to 131°F (55°C)
    • 2A @ 240Vac, all outputs on, up to 158°F (70°C)
    Communications
    • Method: RS-485
    • Application Protocol: BACnet MS/TP
    LED Indicators
    • Power
    • Communications
    • Module Health
    Approvals
    • UL 60730
    • FCC, Part 15, Class A
    • Industry Canada ICES-003, Class A
    • CE Mark
    Application Requirements
    • Opus Version: 5.11 or higher
    • Application Version: 5.11 or higher
  • NameOrder Number
    xio.80 - 8 Universal Inputs/Analog Outputs XIO-8U-B
    xio.08 - 8 Relay Outputs XIO-8DO-B
    xio.08H - 8 Relay Outputs w/HOA XIO-8DO-B-H
    xio.44 - 4 Universal Inputs/Analog Outputs, 4 Relay Outputs XIO-4U4DO-B
    xio.44H - 4 Universal Inputs/Analog Outputs, 4 Relay Outputs w/HOA XIO-4U4DO-B-H
    xio.80CT - 8 Current Transformer Inputs XIO-8CTI-B